Sign In | Join Free | My entremaqueros.com
entremaqueros.com
Products
Search by Category
Home > Analyzers >

0.02% of Accuracy Class Three-phase Meter Test System with ICTs

Categories Stationary Meter Test Equipment
Brand Name: GENY
Model Number: YC1893R
Certification: ISO, CE
Place of Origin: CHINA
MOQ: 1 pcs
Price: negotiation
Payment Terms: L/C,T/T
Supply Ability: 30 pcs per month
Delivery Time: 30 days or order confirmed
Packaging Details: ply wood case
Voltage: 3×240±15%
Frequency: 50 Hz ±15%
Power capacity: > 6 kVA
Power efficient(at full load): ≥85%
Ambient temperature: -10 °C -- +40 °C
Relative humidity: 35% -- 85%
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

0.02% of Accuracy Class Three-phase Meter Test System with ICTs

0.02% of Accuracy Class Three-phase Meter Test System with ICTs


Technical specification for 1~3 position meter test system



The test bench is multiple positions up to 3 meters, 0.02% of accuracy class Three-phase Meter Test System with ICTs, with multiple serial port communication system for parallel communication for testing of smart meters.



Power Source

Voltage

Test voltage output (Phase-Neutral)

3×(24 V – 480 V) or 600 V F-F customized

Power of the voltage output

3×100VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.02% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

< 0.01%

Distortion factor

< 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Current

Test current output

0.3 mA – 120 A

Power of the current output

3×150VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.02% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

< 0.01%

Distortion factor

< 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Phase angle

Range

0 -- 360°

Resolution

0.01°

Setting accuracy

0.1°

Frequency

Range

45 Hz – 65 Hz

Resolution

0.01 Hz


Quality  0.02% of Accuracy Class Three-phase Meter Test System with ICTs for sale
Send your message to this supplier
 
*From:
*To: Guangzhou GENY Electric Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0