Model Number: CLS300 - Standard
Measuring principle: Inverse frequency shift capacitive level detection
Measured variable: Change in picoFarad (pF)
Relay output: 1 SPDT Form C relay
Time delay (ON and/or OFF): 1 ... 60 s
Output: Galvanically isolated
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Pointek CLS300 - Standard

Pointek CLS300 (standard version) is an inverse frequency shift capacitance level and material detection switch with optional rod/cable choices and configurable output. CLS300 is ideal for detecting liquids, solids, slurries, foam, and interfaces in demanding conditions where high pressure and temperatures are present and has the ability to tune out buildup on the probe.

7ML5650-.....-....
CLS300,STANDARD,ROD VERSN,THREAD/FLANGE
7ML5651-.....-....
CLS300,ANALOG,CABLE VERSN,THREAD/FLANGE
7ML5652-.....-....
CLS300,ANALOG,HIGH TEMP ROD,THREAD/FLANG

Related products

Part NumberDescription
7ML1830-1APEASY AIMER II, ALUMINIUM, 3/4 INCH NPT WITH 1 INCH GALVANIZED COUPLING
7ML1830-1AQEASY AIMER II, ALUMINIUM, 3/4 INCH NPT WITH 3/4 - 1 INCH PVC COUPLING
7ML1830-1JACABLE GLAND, 1/2" NPT, General Purpose DIP
7ML1830-1JBCABLE GLAND, 1/2" NPT, explosion proof
7ML1830-1JCM20 x 1.5 cable gland (general use and dust explosion protection)
7ML1830-1JDCABLE GLAND, M20 x 1.5 HF, (EP)
7ML1830-1JETest Magnet
7ML1830-1JFAMPLIFIER / POWER SUPPLY DIGITAL VERSION
7ML1830-1JKLCD DISPLAY FOR CLS 200, DIGITAL
A5E01163688Kit, 316L stainless steel cable extension, 1 Meter, CLS300/LC300
A5E01163689Kit, 316L stainless steel cable extension, 3 Meter, CLS300/LC300
A5E01163690Kit, 316L stainless steel cable extension, 5 Meter, CLS300/LC300
A5E01163691Kit, 316L stainless steel cable extension, 10 Meter, CLS300/LC300
A5E01163693Kit, 316L stainless steel cable extension, 15 Meter, CLS300/LC300
A5E01163695Kit, 316L stainless steel cable extension, 20 Meter, CLS300/LC300
A5E01163698Kit, 316 stainless steel PFA cable extension, 3 METER, CLS300
A5E01163699Kit, 316 stainless steel PFA cable extension, 5 METER, CLS300
A5E01163700Kit, 316 stainless steel PFA cable extension, 10 METER, CLS300
A5E01163701Kit, 316 stainless steel PFA cable extension, 15 METER, CLS300
A5E01163702Kit, 316 stainless steel PFA cable extension, 20 METER, CLS300
A5E01163719Kit, 316L stainless steel rod 180 mm (7.09")
A5E01163720Kit, 316L stainless steel rod 330 mm (12.99")
A5E01163721Kit, 316L stainless steel rod 580 mm (22.83")
A5E01163722Kit, 316L stainless steel rod 830 mm (32.68")
A5E01163723Replacement electronics with driver, CLS300 standard. For use with rod or Cable versions with maximum length of 5 m

Benefits
Active-Shield technology so measurement is unaffected by material buildup or nozzle interference in active shield section
Performs in extremely abrasive conditions because of solid rod construction
Three LED indicators for adjustment control, output status, and power
High-temperature version up to 400 °C (752 °F)

Application
Pointek CLS300 standard version has three LED indicators with basic relay and solid-state switch alarms.

The robust design of CLS300 makes it specifically applicable for heavy solids applications where abrasive materials occur as in the mining industry. The fully potted electronics are unaffected by condensation, dust or vibration.

Wetted parts are made of stainless steel with a PFA shield for high chemical resistance, and of ceramic and stainless steel for high temperature version. Materials with low or high dielectric constants can be accurately detected. The unique Active Shield suppresses interference from material buildup or long installation nozzles.

The unique modular design of the Pointek CLS300 provides a wide range of configurations, process connections, extensions and approvals to meet the temperature and pressure requirements of specific applications. The modular design makes ordering easier and reduces stocking requirements. A wide range of probe configurations are available, including rod and cable versions.

Key Applications: liquids, slurries, bulk solids, relatively high pressure and temperature, hazardous areas, milling and mining applications

Configuration

Technical specifications

Pointek CLS300 - Standard


Mode of operation


Measuring principle

Inverse frequency shift capacitive level detection

Input


Measured variable

Change in picoFarad (pF)

Output


Output signal


  • Relay output

1 SPDT Form C relay

  • Max. contact voltage
  • 30 V DC
  • 250 V AC
  • Max. contact current
  • 5 A (DC)
  • 8 A (AC)
  • Max. switching capacity
  • 150 W (DC)
  • 2 000 VA (AC)
  • Time delay (ON and/or OFF)

1 ... 60 s

  • Solid-state output

  • Output

Galvanically isolated

  • Protection

Against reversed polarity (bipolar)

  • Max. switching voltage
  • 30 V (DC)
  • 30 V peak (AC)
  • Max. load current

82 mA

  • Voltage drop

< 1 V, typical at 50 mA

  • Time delay (pre or post switching)

1 ... 60 s

Accuracy


Resolution


  • Min. sensitivity (pF)

1 % change in actual capacitance

  • Max. temperature error

0.2 % of actual capacitance value

Rated operating conditions1)


Installation conditions


  • Location

Indoor/outdoor

Ambient conditions


  • Ambient temperature

-40 ... +85 °C (‑40 ... +185 °F)2)

  • Storage temperature

‑40 ... +85 °C (‑40 ... +185 °F)

Medium conditions

Liquids, bulk solids, slurries and interfaces, and applications with viscous materials

  • Relative dielectric constant εr

Min. 1.5

  • Process temperature

  • Rod/Cable version

-40 ... +200 °C (-40 ... +392 °F)2)

  • High-temperature version

-40 ... +400 °C (-40 ... +752 °F)

  • Process pressure3)

-1 ... +35 bar g (-14.6 ... +511 psi g)

Design


Material (enclosure)

Powder-coated aluminum with gasket

Degree of Protection

Standard: Type 4/NEMA 4/IP65
Optional: Type 4/NEMA 4/IP68

Cable inlet

2 x M20 x 1.5 thread (option: 2 x ½" NPT conduit entry including 1 plugged entry)

Controls and displays


Displays

3 LEDs, for probe status, output status and power supply

Potentiometers

2 potentiometers for time delay and sensitivity

Switches

5 DIP switches for delay on/off, fail-safe high/low, time delay test/adjust, high/low sensitivity, test delay settings

Power supply


Supply

12 ... 250 V AC/DC, 0 ... 60 Hz, galvanically isolated, 2 W

Certificates and approvals


General Purpose

CSA, FM, CE, UKCA, RCM

Flameproof Enclosure with IS Probe

ATEX II 1/2 G Ex ia/db [ia Ga] IIC TX Ga/Gb,
ATEX II 1/2 D Ex ia/tb [ia Da] IIIC TX Da/Db

UKEX II 1/2 G Ex ia/db [ia Ga] IIC TX Ga/Gb,
UKEX ATEX II 1/2 D Ex ia/tb [ia Da]
IIIC TX Da/Db

Dust Ignition Proof with IS Probe

ATEX II 1/2 D Ex ia/tb [ia Da] IIIC TX Da/Db

UKEX II 1/2 D Ex ia/tb [ia Da] IIIC TX Da/Db

CSA/FM Class II, Div. 1, Groups E, F, G
CSA/FM Class III T4

Explosion Proof Enclosure with IS Probe

CSA/FM Class I, Div. 1,
Groups A, B, C, D

CSA/FM Class II, Div. 1,
Groups E, F, G

CSA/FM Class III T4

Marine

Lloyds Register of Shipping, Categories ENV1, ENV2, and ENV5

Overfill Protection

WHG (Germany)
VLAREM II (Belgium)

Others

Pattern Approval (China)


Quality Pointek CLS300 - Standard for sale
Send your message to this supplier
 
*From:
*To: Xi'an Kacise Optronics Co.,Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0