| Sign In | Join Free | My entremaqueros.com |
|
| Categories | ABB Spare Parts |
|---|---|
| Brand Name: | ABB |
| Model Number: | AO810V2 |
| Certification: | COO & COC |
| Place of Origin: | Germany |
| MOQ: | 1 pc |
| Price: | $111-$123 |
| Payment Terms: | T/T,paypal,alipay |
| Supply Ability: | 99+ |
| Delivery Time: | 3-5 days |
| Packaging Details: | Brand new and original |
| Shipping Weight: | 0.2 KG |
| Packing Size: | 10.2 x 11.1 x 7.2 cm |
| Condition: | Brand new and original |
| Warranty: | One year |
| Trade Terms:: | EXW, DAP, FOB, CIF |
| Express Delivery: | DHL, FedEx, UPS |
| Company Info. |
| Xiamen Changxuyuan Trading Co., Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
AO810V2 3BSE038415R1 ABB Analog output module AC 800M System 800 A8
The ABB AO810V2 is the second-generation 8-channel analog output module in the AC 800M distributed control system, specifically designed for 4-20mA signal output applications in industrial automation. As an upgraded version of the classic AO810, the AO810V2 maintains high compatibility while optimizing diagnostic functions, anti-interference capabilities, and long-term stability. It is suitable for driving field devices such as electric control valves, frequency converters, actuators, and recorders.
Core features
8-channel independent analog output
Output signal: 4-20 mA (default), which can be configured by
software as 0-20 mA
Load capacity: Maximum 750 Ω (@24V DC)
Output accuracy: ±0.1% of span (typical value, 25°C)
High-reliability design
Electrical isolation between channels: ≥ 500 V AC
Short-circuit protection: All output channels are equipped with
automatic current limiting and recovery functions
Open circuit detection: Optional to enable (through software
configuration)
Technical parameters
Process control loop: Electrical valve positioner (I/P converter)
for driving pneumatic control valves
Motor speed control system: Sends a 4-20mA speed setting signal to
the frequency converter
Boiler and Combustion control: Adjust the opening degree of the
fuel valve and the position of the damper
Water treatment plant: Control the stroke of the dosing pump and
the dosage of flocculant
Test and calibration bench: Serves as a standard signal source to
output precise current values
Installation and Usage instructions
Hardware installation
Insert the AO810V2 into the S800 I/O electronic rack (such as
TB840A);
Connect to the CI854A (optical fiber) or CI801 (electrical)
communication module via the ModuleBus cable;
Connect the output terminals to the on-site execution equipment
using shielded cables.
Software configuration
Create an instance of the AO810V2 device in Control Builder M;
Set for each channel:
Output range (4-20 mA or 0-20 mA
Engineering units (%, Hz, °C, etc.)
Alarm limit values and fault actions (such as output hold/reset to
zero during a fault)
Enable the "Open Circuit Detection" function (optional);
Download the configuration to the AC 800M controller.
Debugging and verification
The green LED on the front panel indicates that the module is
operating normally.
If a certain channel is short-circuited, the corresponding channel
will limit the current and report the fault.
Loop testing can be performed by forcing the output value through
Control Builder M.