Sign In | Join Free | My entremaqueros.com
entremaqueros.com
Products
Search by Category
Home > Chemical Machinery & Equipment >

Emerson Rosemount 3051TG3A2B21AB4E5Q4 Process Management, Rosemount Division Dust Ignition-Proof

Categories Pressure Temperature Transmitter
Brand Name: Rosemount
Model Number: 3051TG3A2B21AB4E5Q4
Certification: CE, ect
Place of Origin: Singapore
MOQ: 1
Price: Negotiation
Payment Terms: T/T
Supply Ability: In Stock
Delivery Time: 3-5days
Packaging Details: New Original Box
Product Category: Pressure Transmitters
Product Number: 3051TG3A2B21AB4E5Q4
City of origin: Singapore
Lead time: 6weeks
Packing: Carton
Pressure Measurement: Gauge
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Emerson Rosemount 3051TG3A2B21AB4E5Q4 Process Management, Rosemount Division Dust Ignition-Proof


Emerson Rosemount 3051TG3A2B21AB4E5Q4 Process Management, Rosemount Division Dust Ignition-Proof

Product Description of 3051TG3A2B21AB4E5Q4

Product Highlights Rosemount 3051T In-line Pressure transmitters provide reliable Gage and Absolute pressure measurement in a compact in-line design Gage -14.7 to 800 psi (-1.0 to 55 bar) 0 to 800 psia (0 to 55 bar) 4–20 mA with Digital Signal Based on HART Protocol 1/2–14 NPT Female 316L SST Silicone Aluminum Bracket for 2-in. Pipe or Panel Mounting, All SST FM Explosion-proof, Dust Ignition-proof Calibration Certificate


Verifying configuration parameters of 3051TG3A2B21AB4E5Q4
Emerson recommends verifying the following configuration parameters prior to
installation into the process:
• Alarm and Saturation Values
• Damping
• Process Variables
• Range Values
• Tag
• Transfer Function
• Units
Verify configuration parameters with a communication device of 3051TG3A2B21AB4E5Q4
Procedure
1. Go to Device Settings → Setup Overview → Alarm and Saturation Values to set
alarm and saturation levels.
2. Go to Device Settings → Setup Overview → Output to set damping.
3. Set the process variables:
a) To set the primary variable, go to Device Settings → Output → Analog Output
→ PV Setup.
b) To set up the other process variables, go to Device Settings →
Communication → HART → Variable Mapping.
4. To set range values, go to Device Settings → Output → Analog Output → PV Setup.
5. To set a tag, go to Device Settings → Setup Overview → Device.
6. To set transfer function, go to Device Settings → Output → Analog Output → PV
Setup.
7. Set units:
a) To set pressure units, go to Device Settings → Output → Pressure → Setup.
b) To set other units, go to Device Settings → Output → Pressure/Flow/
Totalizer/Level/Volume/Module Temperature → Setup.