| Sign In | Join Free | My entremaqueros.com |
|
| Categories | Medium Voltage Power Cables |
|---|---|
| Name: | Medium Voltage cables |
| Rated voltage: | 6/10 kV; 12/20 kV; 18/30 kV; 20,8/36 kV. |
| Cable standard: | DIN VDE 0267-620. |
| Operating temperature, short circuit: | 250° C. |
| Minimum installation temperature: | -20° C. |
| Halogen free: | EN 60332-1. |
| Place of Origin: | Guangzhou, China |
| Brand Name: | SUNWIN |
| Certification: | ISO9001, ISO14001, OHSAS18001 |
| MOQ: | Negotiable |
| Price: | Negotiable |
| Packaging Details: | 100 m / tied, or customized |
| Delivery Time: | 10 day |
| Payment Terms: | 30% deposit, the balance is settled on the delivery date |
| Supply Ability: | 100,000 m / month |
35KV XLPE Insulation Medium Voltage Power Cables Lead Free Black Outer Sheath Color
NA2XS(F)2Y medium voltage aluminium power cable - Construction
1. Stranded (RM) aluminium wires.
2. Inner layer of semi-conducting material.
3. Core insulation of cross-linked polyethylene.
4. Outer layer of semi-conducting material.
5. Swellable tape.
6. Screen of copper wires.
7. Anti-twist tape.
8. Outer sheath of polyethylene (PE), black.
NA2XS(F)2Y medium voltage aluminium power cable - Technical data
and tests
Rated voltage : 6/10 kV; 12/20 kV; 18/30 kV; 20,8/36 kV.
Cable standard : DIN VDE 0267-620.
Operating temperature, short circuit : 250° C.
Max. conductor temperature in service : 90° C.
Minimum installation temperature : -20° C.
Halogen free : EN 60332-1.
Lead free.
UV stability.
NA2XS(F)2Y medium voltage aluminium power cable - Applications
NA2XS(F)2Y - 6/10 kV; 12/20 kV; 18/30 kV; 20,8/36 kV - medium
voltage power cable for static application in ground, within and
outside facilities, outdoor, in cable canals, in dry areas or in
water.
PE sheath secures increased mechanical resistance during and after
laying. Swellable tape blocks water spreading within the cable.
Due to its very low factor of dielectric loss, which remains
constant over its entire operating lifetime, and owing to excellent
insulation property of XLPE-material, firmly longitudinally spliced
with inner and external screen of semi-conductive material
(extruded in one process), the cable has a high operating
reliability.
This cable can be used in switching blocks, transformer stations,
industrial plants and in electric power plants.
To avoid the effects of external impact, the adhering
semi-conductive layer extruded between conductor and insulation,
along with concentric copper conductor, secures restriction of
electric field and resistance to partial discharges.
|