Sign In | Join Free | My entremaqueros.com |
|
Categories | 220vdc To 220vac Inverter |
---|---|
Brand Name: | TBB |
Model Number: | TM252EX1 |
Certification: | CE,ISO9000 |
Place of Origin: | China |
MOQ: | 1piece |
Price: | Negotiable |
Payment Terms: | T/T |
Delivery Time: | 1-3days depends on batch order qty |
Packaging Details: | Carton, Plywood pallet |
Model: | TM252EX1 |
AC output: | 220Vdc in to 220Vac out |
Communication Interface: | Relay dry contact x 6 |
DC input: | 220VDC |
Output frequency: | 50HZ |
Protocol: | RS232 |
Efficiency: | 89% |
Input voltage: | 110v/120v/220v/230v |
Output type: | Single |
Output waveform: | Pure Sine Wave Output |
Application: | Telecom |
Display: | LED+LCD |
Company Info. |
TBB Power Co., Ltd. |
View Contact Details |
Product List |
Combined with modern semiconductors with high switching frequencies
technology, TM250 inverter module features compact construction,
low weight and high efficiency. TM250 inverter is able to run in
parallel supporting hot plug, of which is suitable to compose small
or medium modular inverter system .
Structure
Monitor | |
Display | |
LCD | 4x16 character |
LED | working status |
Alarm | LED, audible |
Communication Interface | RS485 and RS232 |
Relay dry contact x 6 Auxiliary contacts x 16 | |
STS | |
Input | |
Voltage range | :-25% - +20% |
Frequency range | : ±10% |
Output | |
Work mode | AC priority or inverter priority |
Transfer time | 4ms |
Rated power | Various |
Specification
110VDC ,125VDC&220VDC
Model | TM251 | TM252 | TM253 |
Electrical | |||
Nominal DC input | 110Vdc,125Vdc or 220Vdc | ||
DC operating range | Refer to 2.3 on Page 9 | ||
Output power | 1Kva | 1.5Kva | 2Kva |
Wave form | Pure sine wave | ||
Power factor | 0.8 | ||
Norminal output | 110Vac 115Vac 120Vac 127Vac 220Vac 230Vac 240Vac (±2%) | 220Vac 230Vac 240Vac (±2%) | |
Output frequency | 50/60Hz ± 1% | ||
THD | <3% liner load | ||
<5% non-liner load | |||
Crest factor | 3:1 | ||
Efficiency | Max 88% / 89% | ||
Overload | 150% 1min | 150% 10s | |
125% 10mins | 125% 1min | ||
Dynamic response time | < 20ms | ||
Others | |||
Operating Temp. | Full load, -10℃ - 40℃ | ||
Isolation | 1500Vrms | ||
Safety | EN60950-1 | ||
Emmission | EN55022 | ||
Immunity | EN55022 |
General Precaution
1.2.1 Do not expose STM250 to dust, rain, snow or liquids of any
type,it is designed
for indoor use. DO NOT block off ventilation, otherwise the
INVERTER would
be overheating.
1.2.2 To avoid fire and electric shock, make sure all cables
selected with right
gauge and being connected well. Smaller diameter and broken cable
are not
allowed to use.
1.2.3 Please do not put any inflammable goods near to inverter.
![]() |