| Sign In | Join Free | My entremaqueros.com |
|
| Categories | Building Materials Flammability Tester |
|---|---|
| Brand Name: | SKYLINE |
| Model Number: | GJL-2 |
| Certification: | CE |
| Place of Origin: | CHINA |
| MOQ: | 1 unit |
| Price: | negotiated |
| Payment Terms: | T/T, L/C, Western Union, MoneyGram |
| Supply Ability: | 1 unit/ month |
| Delivery Time: | 10 work days |
| Packaging Details: | plywood case |
| Standards: | GB 14907-2002 Steel-Structure Fireproof Coating,GB T9978-2008 Fire Resistance Test Method for Building Components, GB T23864-2009 Plugging Material of Fireproof |
| Operating Voltage: | AC 380V±10% 50Hz |
| Air Flow: | 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min |
| Timing Range: | 0-360 min;Timing Accuracy: < +/-2s |
| Maximum of Burning Length of the Sample: | 1600mm |
| Company Info. |
| SKYLINE INSTRUMENTS CO.,LTD |
| Verified Supplier |
| View Contact Details |
| Product List |
Technical indicators
| Operating Voltage | AC 380V +/-10% 50Hz ; Electric power: 3KW |
| Stove Pressure Measurement Range | 0-100Pa Measurement Accuracy: ≤ +/-3Pa |
| Air Flow | 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min |
| Burning Airflow | Propane ,Liquefied gas |
| Gas Flow | 0-100 L/min;Measurement Accuracy:2.5 level |
| Tank Capacity | 50 kg*2 |
| Test Temperature | Program warming:60min room temperature-925℃;120min room temperature-1050℃;180min room temperature-1115℃;240min room temperature-1150℃;300min room temperature-1180℃; 360min room temperature-1210℃; |
| Equipment Precision | a.furnace temperature: +/-15℃;b.internal specimen temperature: +/-10℃; c.backfire specimen temperature: +/-4℃ |
| Temperature Sensor | a.armored platinum rhodium platinum value S thermocouple accuracy class:II level;b.armored nickel-chromium nickel-silicon value K thermocouple accuracy class:II level |
| Timing Range | 0-360 min;Timing Accuracy: < +/-2s |
| Maximum of Burning Length of the Sample | 1600mm |
| Instrument Dimensions | Test plate bracket 670mm*670mm*1100mm;Control box 800mm*500mm*500mm |
Features
1.PLC+NA view professional software, touch screen control, easy
operation
2. The whole process of testing is fully automated
3. Temperature errors are lower than the national standard
Design Standards
GB14907-2002 Steel-Structure Fireproof Coating
GB T9978-2008 Fire Resistance Test Method for Building Components
GB T23864-2009 Plugging Material of Fireproof

|