Strong backup functions
When unit is failed: If one slave unit fails, failed unit will stop
but the others will keep running.
If master unit fails, all the units will stop but any of the slave
one can be set as the master unit by manual setting in a very short
time. When unit is under protection: If master unit’s protection
happens, protected unit will stop but the others will keep running.
If slave unit’s protection happens, protected unit will stop but
the others will keep running .
Except PE, P9 protection happens.(PE:Low temperature protection of
evaporator.
P9:Outlet and inlet water temperature difference protection.)
Modular design
Max.16 can be combined in one system,up to 2000kW after combined.
The modular design facilitates easy expansion in phases to respond
to additional cooling requirements,this solution provides excellent
partial load facility, low initial investment cost.
Wide range of outlet water temperature
Cooling: 5~17°C (7°C is default,set in factory), 0~17°C can be
available by switch the S5 on PCB, the antifreeze must be put into
pipeline.
Heating: 40~50°C (45°C is default, set in factory), 22~50°C can be
available by switch the S4 on PCB.
Reliable protections
High/low pressure protection of compressor.Power phases
protection.Evaporator low temperatureprotection in cooling.System
anti-freezing protection in winter.Frequently ON/OFF protection of
compressor.Over-current protection
of compresor.Air discharge temperature protection of
compressor.System high temperature protection.Water flow
protection.Sensor malfunction protection.